KYN28A-12 Switchgear
| Model Number:KYN28A-12 |
Online Postings: Products , Selling Leads
Country/Territory: China
Business Type: Manufacturer
Number of Employees: 101 - 500 People
1, KYN28A-12 metal-cased closed drawer switch device newly developed by our company is suitable for 3.6~12kV three-phase AC power network of 50Hz.
2, It can be applied to the singular bus, and double bus system
3, Its Shield protection level is IP4X.
4, China-made VS1 series vacuum breaker, as well as VD4 vacuum breaker (made by ABB) is adopted
Standards Adopted
GB3906 3~35 V AC Metal Enclosed Switch Device
GB/T 11022 Technical Requirements on High Voltage Switch Device & Control Device Standards
IEC60298 AC Metal Enclosed Switch and Control Device above 1kV, below 50kV
DL/T404 Technical Requirements for ordering Indoors AC High-Voltage Switch Cabinet
Technical Specification
Items | Unit | Parameters | |||
Rated voltage | kV | 3.6,7.2,12 | |||
Rated frequency | Hz | 50 | |||
Rated current of breaker | A | 630,1250,1600,2000,2500,3150 | |||
Rated current of switch cabinet | A | 630,1250,1600,2000,2500,3150 | |||
Rated dynamic current(4s) | kA | 16,20,25,31.5,40,50 | |||
Rated dynamic current (peak value) | kA | 40,50,63,80,100,125 | |||
Rated short-circuit switch on/off current | kA | 16,20,25,31.5,40,50 | |||
Rated short-circuit switch on/off current(peak value) | kA | 40,50,63,80,100,125 | |||
Rated insulation level | Work frequency withstand within 1min. | kV | 24 | 32 | 42 |
Lightning withstand | kV | 40 | 60 | 75 | |
Protection level | IP4X for shield, IP2X when the doors of isolation and breaker room open | ||||
Dimensions (W×D×H,) | mm | 800×1660×2300 1000×1500×2300 | |||
Technical parameters
Name | Unit | Value | |
Rated operation voltage | Switch-on coil | V | DC220, 110 |
Switch-on coil | V | AC220, 110 | |
Coil power | Switch-on coil | W | 245 |
Switch-on coil | W | 245 | |
Power of power-reservation motor | W | 50 | |
Rated voltage of power-reservation motor | V | DC220, 110 | |
Time for reserving power | s | ≤10 | |
Parameters Required for Design
1, Main wiring diagram, purpose and one-line system diagram, rated voltage, rated current, rated short-circuit switch on/off current, power distribution room layout and switch cabinet arrangement drawing
2, Requirements on control, measurement and protection of switch cabinet
Requirements on lock and automatic equipment, as well as principle diagram
3, Model, specification, and quantity of the main components in the cabinet
If bus bridge is used in switch cabinets, cable entry, rated current-carrying capacity, span, height from ground and so on should be supplied
If the switch cabinet is used under special conditions, introduction in detail needs to be supplied
KYN28A-12 Switchgear
Other products
See more
Switchgear, high voltage switchgear, switch cabinet products from this supplier.
Related Searches: Switchgear, High Voltage Switchgear, Switch Cabinet
Products
- Soft starters [7]
- motors [2]
- Power quality products [5]
- Switchgear [3]
- Switch Cabinet [3]
Contact Us
Shanghai Surpass Sun Electric Co., Ltd.
[China]
Street Address : 36 Nujiang Road, Putuo District
City : Shanghai
Province/State : Shanghai
Country/Region : China